Custom Control Programming,
Fields 3 & 4 (continued)
Technical Manuals Online! - http://www.tech-man.com
Continued
FIRE
When using the input condition qualifier FIRE, a statement is true when the
point indicated in Field 4 is in the FIRE state. Field 4 Choices for the FIRE
qualifier are:
System Card Points
Digital Pseudo Points
Note:
The statement holds true until the system is no longer in the
FIRE state.
When the condition of 3-01 is FIRE, the input is true, and the output is executed.
If the system is not reset, and the condition of 3-02 becomes FIRE after 3-01, the
system outputs ignore 3-02. In other words, if the output executes from the
FIRE condition of 3-01, the output will not re-execute from the FIRE condition
of 3-02.
Field 1
FIRST
[
]
STATEMENT
SECOND
[OR]
STATEMENT
Example: The condition of 3-01 is FIRE. The 4010 is reset from the
Fire Alarm Control Panel (FACP). After the system is reset (and there are no
alarms) the condition of 3-02 is FIRE. The appropriate notification appliances
now activate for the FIRE condition of 3-02.
FIRE DET
When using the input condition qualifier FIRE DET (Fire Detect), a statement is
true when the point indicated in Field 4 is activated. Field 4 Choices for the
FIRE DET qualifier are:
IDNet Points
Digital Pseudo Points
Note:
When using the FIRE DET qualifier, the statement holds true for
one 4010 polling cycle (typically less than one second). This
allows the output to re-execute after a signal silence.
Field 2
Field 3
[
]
[FIRE]
[
]
[FIRE]
Figure 8-19
8-17
Field 4
[3-01]
[3-02]
Continued on next page