Auto Detect NEW Hardware

Overview

Procedure

Technical Manuals Online! - http://www.tech-man.com
This option adds new hardware that is not currently in the CFIG. All existing
hardware and programming remains the same.
1.
Press <MENU>.
Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
2.
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue with the Quick-CFIG option.
Press <NEXT> or <PREVIOUS> until <AUTO DETECT NEW
4.
HARDWARE> is displayed and then press <ENTER>. A warning
appears, indicating that this will change the current configuration.
WARNING
<Enter> to Continue
This will CHANGE current configuration
5.
Press <ENTER> to continue. Another warning appears, indicating that you
need to press <ENTER> to confirm the hardware detection operation.
WARNING
<Enter> to Continue
Press <Enter> to confirm Detect NEW
A message appears indicating that Quick CFIG is reconfiguring the hardware.
This message is followed by another, which indicates that Quick CFIG is
scanning for IDNET devices. The Auto Detect NEW Hardware function is
complete when a message similar to the following appears.
** Automatic Hardware Detection Completed **
Total IDNet Devices Added: 128
Refer to "Save CFIG Option" at the end of this chapter for information on saving