Enable City Circuit

Overview

Setting the Enable City Circuit
Option
Technical Manuals Online! - http://www.tech-man.com
You must enable the City Circuit via the 4010 System Options menu when
installing the city circuit card. The default setting for the city circuit is OFF.
Use the following steps to set the Enable City Circuit option on the 4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<ENABLE CITY CIRCUIT > is displayed and then press <ENTER>.
Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then
6.
press Enter.
7.
Follow the prompts to confirm this action.