Continue, Restore CFIG, and Save CFIG

Continue

Restore CFIG

Save CFIG

Technical Manuals Online! - http://www.tech-man.com
The Continue option allows you continue an edit session without saving or
restoring the information stored in the Edit Buffer to the CFIG. This option
appears when you use the Exit/Clear button to back out of programming mode.
The Restore CFIG option restores all information to the 4010 configuration prior
to any programming modifications. Select this option if you do not wish to save
any edits or modifications you made during your programming session to the
4010 configuration.
You can restore a CFIG by choosing the menu option as described below or by
pressing Exit/Clear to back out of Programming mode and then choosing the
Restore CFIG option from the 4010 prompts. In both cases, your 4010 re-boots
and becomes operational as a fire alarm system.
To access the Restore CFIG menu option, follow these steps:
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
4.
Press <NEXT> or <PREVIOUS> until <RESTORE CFIG> is displayed
and then press <ENTER>.
The Save CFIG option saves all information to the 4010 configuration after or
during programming. Choose this option if you wish to save all of your edits
and modifications you made during your programming session to the 4010
configuration.
You can save CFIG by choosing the menu option as described below or by
pressing Exit/Clear to back out of Programming mode and then choosing the
Save CFIG option from the 4010 prompts. In both cases, your 4010 re-boots
and becomes operational as a fire alarm system.
To access the Restore CFIG menu option, follow these steps:
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
4.
Press <NEXT> or <PREVIOUS> until <SAVE CFIG> is displayed and
then press <ENTER>.
When exiting the programming mode, your 4010 re-boots and becomes
operational as a fire alarm system.