Restore Factory CFIG

Overview

Procedure

Technical Manuals Online! - http://www.tech-man.com
This option restores the 4010 to its original (factory default) CFIG. All pseudo
points (Analog and Digital) are cleared, Custom Control is erased, etc.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue with the Quick-CFIG option.
4.
Press <NEXT> or <PREVIOUS> until <RESTORE FACTORY
CONFIG.> is displayed and then press <ENTER>. A warning appears,
indicating that this will delete the current configuration.
WARNING
<Enter> to Continue
This will DELETE current configuration
5.
Press <ENTER> to continue. The following message appears, indicating
that the system is restoring the factory default configuration.
**
Restoring Factory Default Panel
This message is followed by a series of internal test messages. The High-Level
Status screen appears when the operation is complete.
4-4
WARNING
**