You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set
duration. The range for the Silence/Reset Inhibit timer is 0-60 minutes with zero
(No Inhibit) being the default setting.
Use the following steps to set the Silence/Reset Inhibit timer on the 4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<SILENCE/RESET INHIBIT> is displayed and then press <ENTER>.
6.
Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and
then press Enter.
7.
Follow the prompts to confirm this action.