Hardware Device Types,
TrueAlarm Levels and
Sensitivities
Monitor Hardware Device
Types
Technical Manuals Online! - http://www.tech-man.com
Continued
Sensitivities and corresponding levels are shown in Table A-2 for TrueAlarm
types.
Table A-2. TrueAlarm Levels and Sensitivities
Levels
PHOTOs
Level 1
0.5%
1.0%
Level 2
1.5%
Level 3
2.0%
Level 4
Level 5
2.5%
3.0%
Level 6
3.7%
Level 7
Table A-3 lists the Monitor Hardware Device Types for the 4010.
Table A-3. Monitor Hardware Device Types
Device Type
MAZAM
MBZAM
ADRPUL
SIAM
CANPUL
KACPUL
A-3
Sensitivities
XPHOTOs
IONs
0.2%
0.5%
117°F (X°C)
0.5%
0.9%
135°F (57°C)
1.0%
1.3%
155°F (68°C)
1.5%
1.7%
155°F (68°C)
2.0%
1.7%
155°F (68°C)
2.5%
1.7%
155°F (68°C)
3.7%
1.7%
155°F (68°C)
Description
Class A Monitor ZAM (T-sense)
Class B Monitor ZAM (T-sense)
Addressable Pull Station
Supervised IAM (T-sense)
Canadian 2-stage Pull Station
International KAC Pull Station