Edit Settings For System Options; Overview; Procedure - Simplex 4010 Installing And Operating Insructions

Front panel
Hide thumbs Also See for 4010:
Table of Contents

Advertisement

Edit Settings for System Options

Overview

Procedure

Time/Date Format
Active Status Reminder
Alarm Silence/Reset Inhibit
Alarm Cut-out Timer
Door Drop on Alarm
Door Drop on AC Power Loss
Audible NAC Operation
Technical Manuals Online! - http://www.tech-man.com
Once this action is selected from the Quick CFIG menu, you can set these
options by scrolling through the choices shown in Table 4-1 and selecting the
appropriate settings for each. For timer options, selecting "0"initiates the action
immediately.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue with the Quick-CFIG option.
4.
Press <NEXT> or <PREVIOUS> until <EDIT SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5. Use the <NEXT> and <PREVIOUS> keys to scroll through the system
options. Edit each of the system options as necessary, using the information
in Table 4-1. Refer to Chapter 7 for specific information on system options.
Table 4-1. System Options and Available Settings
System Option
Choose 12 or 24-Hour Format
Choose:
On/Off; default Off
Set Reminder Interval (1-12 Hours); default = 8
Signal Duration (0-60 Secs.) 0=ON til clear
default = 5
Choose a timer range from 0 - 60 Mins; default = 0
Choose a timer range from 0 - 60 Mins; default = 0
Choose a timer range from 0 - 60 Secs; default = 0
Choose a timer range from 0 - 60 Mins; default = 0
Choose:
Audible NACs: Steady
Audible NACs: Slow March
Audible NACs: Fast March
Audible NACs: Temporal (default)
4-6
Settings
Continued on next page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents