Simplex 4010 Installing And Operating Insructions page 170

Front panel
Hide thumbs Also See for 4010:
Table of Contents

Advertisement

Software Point Types,
TrueAlert Non-Addressable
Point Types
Technical Manuals Online! - http://www.tech-man.com
Continued
TrueAlert Non-Addressable operation for a particular NAC is enabled by
selecting the QALERT software point types. Two types of points exist – one
under system control and one with no system mode, which allows you to use
Custom Control to perform selective signaling.
Table A-8. TrueAlert Non-Addressable Point Types
Point Type
QALERT
SQALERT
A-8
Description
This point type has no automatic operation.
All operations for this point type must be
programmed using Custom Control.
When the SQALERT point type is selected,
the system does the following:
-
Automatically turns ON the designated
circuit on alarm detect.
-
Issues the Horn Silence command upon
Alarm Silence.
-
Turns OFF the circuit at the completion of
System Reset.
Any point programmed with this point type will
not be available for Custom Control
programming.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4010 and is the answer not in the manual?

Questions and answers

Pete
March 7, 2025

On a 4010 what is point label 4009A trouble. I **** not familiar with this

User image 67cb254f3b885

Table of Contents

Save PDF