Software Point Types,
TrueAlert Non-Addressable
Point Types
Technical Manuals Online! - http://www.tech-man.com
Continued
TrueAlert Non-Addressable operation for a particular NAC is enabled by
selecting the QALERT software point types. Two types of points exist – one
under system control and one with no system mode, which allows you to use
Custom Control to perform selective signaling.
Table A-8. TrueAlert Non-Addressable Point Types
Point Type
QALERT
SQALERT
A-8
Description
This point type has no automatic operation.
All operations for this point type must be
programmed using Custom Control.
When the SQALERT point type is selected,
the system does the following:
-
Automatically turns ON the designated
circuit on alarm detect.
-
Issues the Horn Silence command upon
Alarm Silence.
-
Turns OFF the circuit at the completion of
System Reset.
Any point programmed with this point type will
not be available for Custom Control
programming.