Custom Control Programming
To Start Custom Control
Programming
Technical Manuals Online! - http://www.tech-man.com
You must log in at the appropriate level and use the following steps to begin a
Custom Control session.
1.
From the High-Level Status screen, press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [Programming] is displayed and
then press <ENTER>. Figure 8-1 appears briefly to warn you that the 4010
is no longer in the Fire Alarm Operation mode.
Please Wait. . .
Fire Alarm Operation Suspended
Figure 8-1. Fire Alarm Operation Suspended Screen
3.
A confirmation screen appears. Follow the prompts to enter programming.
Press <NEXT> or <PREVIOUS> to select [Custom Control] and then
press <ENTER>.
8-7
Continued on next page