4098 TrueAlarm SENSORS

General Notes

This section contains general notes, specifications, and mounting information for
the TrueAlarm Smoke and Heat Sensors shown in Table 5.
WARNING: Be sure that the location of each smoke sensor and each heat sensor
has been planned per local and national fire codes (see NFPA 72,
Chapter 5).
1.
Smoke sensor sensitivities are set and continuously monitored by the control
panel. This functionality complies with NFPA 72, Chapter 7. When
functional testing of these sensors is required per NFPA 72, use the test
methods described in the Maintenance and Testing section of this
publication.
2.
Refer to NFPA 72 for application, test, and maintenance requirements.
3.
The 4098-9733 heat sensor and 4098-9754 multi-sensor provide a rate-of-
rise function that is software programmed and selectable at 15° F (8.3° C) or
20° F (11.1° C) per minute. The 4098-9733 and 4098-9754 also provide
general temperature monitoring within the range of 32°-122° F (0°-50° C).