Advertisement

5.12

Step 8. Configuring Cards

The all cards and modules in the CPU FACU back box must be configured to operate correctly in the system via their DIP switch and
jumper ports. This section describes the hardware configuration for the CPU components.
5.12.1
RUI+ Master Motherboard Configuration
The CPU motherboard must be jumpered as follows (refer to Figure 91):
RUI+ Isolation:
By default the RUI channel of the RUI+ Master motherboard is set to isolated mode. This provides better noise immunity in larger systems.
If you are using an RUI+ Master Motherboard to connect to a 4602-9101 (SCU), 4602-9102 (RCU) or 4602-9150/4602-7101 (SCU/RCU
Graphic Command Center), move jumpers P5 and P6 to the RUI NON ISO position.
P5 and P6
Position 1-2: RUI is isolated (default)
Position 2-3: RUI is not isolated (use for RCU/SCU compatibility)
SW1 and SW2 are used to set the CPU motherboard up to be attached to either a network card or a RS-232/2120 card.
• On: Network card (NIC) attached to CPU motherboard (default).
• Off: RS-232/2120 card attached to CPU motherboard.
Note:
SW1: (Top) ON is to the left.
SW2: (Bottom) On is to the right.
5.12.2

Master Controller Daughter Card Configuration

The master controller daughter card must be jumpered as follow (refer to Figure 87):
P1 is used for engineering diagnostics (COMLAB).
• Position 1 – 2: Download or no connection.
• Position 2 – 3: Diagnostic mode.
P3 configures the RAM battery as ON or OFF.
• Position 1 – 2: ON.
• Position 2 – 3: OFF.
page 57
4100ES Fire Alarm System Installation Guide
574-848