Parameters: 10-** Devicenet Can Fieldbus - Danfoss FC 300 Programming Manual

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
9-94 Changed Parameters (5)
Array [116]
No LCP Address
Read only
Range:
3
3
0 N/A
[0 - 9999 N/A] This parameter displays a list of all the
*
3.12 Parameters: 10-** DeviceNet CAN
Fieldbus
3.12.1 10-0* Common Settings
10-00 CAN Protocol
Option:
[0]
CANopen
[1]
DeviceNet
*
NOTE
The options depend on installed option.
10-01 Baud Rate Select
Select the fieldbus transmission speed. The selection must
correspond to the transmission speed of the master and the other
fieldbus nodes.
Option:
[16]
[17]
[18]
[19]
[20]
*
[21]
[22]
10-02 MAC ID
Range:
Application
dependent
*
10-05 Readout Transmit Error Counter
Range:
0 N/A
[0 - 255 N/A] View the number of CAN control transmis-
*
10-06 Readout Receive Error Counter
Range:
0 N/A
[0 - 255 N/A] View the number of CAN control receipt
*
114
FC 300 Programming Guide
Function:
frequency converter parameters deviat-
ing from default setting.
Function:
View the active CAN protocol.
Function:
10 Kbps
20 Kbps
50 Kbps
100 Kbps
125 Kbps
250 Kbps
500 Kbps
Function:
[Application
Selection of station address.
dependant]
Every station connected to the
same network must have an
unambiguous address.
Function:
sion errors since the last power-up.
Function:
errors since the last power-up.
MG.33.M9.02 - VLT
10-07 Readout Bus Off Counter
Range:
Function:
0
[0 - 255 ] View the number of Bus Off events since the last
*
power-up.
3.12.2 10-1* DeviceNet
Parameters specific to the DeviceNet fieldbus.
10-10 Process Data Type Selection
Option:
Function:
Select the Instance (telegram) for data
transmission. The Instances available are
dependent upon the setting of
par. 8-10 Control Profile.
When par. 8-10 Control Profile is set to [0] FC
profile, par. 10-10 Process Data Type Selection
options [0] and [1] are available.
When par. 8-10 Control Profile is set to [5]
ODVA, par. 10-10 Process Data Type Selection
options [2] and [3] are available.
Instances 100/150 and 101/151 are Danfoss-
specific. Instances 20/70 and 21/71 are ODVA-
specific AC Drive profiles.
For guidelines in telegram selection, please
refer to the DeviceNet Operating Instructions.
Note that a change to this parameter will be
executed immediately.
[0]
INSTANCE
*
100/150
[1]
INSTANCE
101/151
[2]
INSTANCE
20/70
[3]
INSTANCE
21/71
10-11 Process Data Config Write
Select the process write data for I/O Assembly Instances 101/151.
Elements [2] and [3] of this array can be selected. Elements [0] and
[1] of the array are fixed.
Option:
[0]
None
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow Down Value
[341]
Ramp 1 Ramp up Time
[342]
Ramp 1 Ramp Down Time
[351]
Ramp 2 Ramp up Time
[352]
Ramp 2 Ramp down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[411]
Motor Speed Low Limit [RPM]
[412]
Motor Speed Low Limit [Hz]
[413]
Motor Speed High Limit [RPM]
®