Settings; Ied Status For Iec 60870-5-103 I103Ied; Functionality - ABB Relion 650 Series REB650 Technical Manual

Busbar protection
Table of Contents

Advertisement

1MRK 505 288-UEN A
12.22.4
Table 329:
I103FLTPROT Non group settings (basic)
Name
Values (Range)
FunctionType
12.23
12.23.1
Technical manual
Name
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC

Settings

Unit
1 - 255
-

IED status for IEC 60870-5-103 I103IED

Functionality

I103IED is a function block with defined IED functions in monitor direction. This
block uses parameter as FunctionType, and information number parameter is defined
for each input signal.
Type
Default
Description
BOOLEAN
0
Information number 76, signal transmitted
BOOLEAN
0
Information number 77, signal received
BOOLEAN
0
Information number 78, zone 1
BOOLEAN
0
Information number 79, zone 2
BOOLEAN
0
Information number 80, zone 3
BOOLEAN
0
Information number 81, zone 4
BOOLEAN
0
Information number 82, zone 5
BOOLEAN
0
Information number 84, start general
BOOLEAN
0
Information number 85, breaker failure
BOOLEAN
0
Information number 86, trip measuring system
phase L1
BOOLEAN
0
Information number 87, trip measuring system
phase L2
BOOLEAN
0
Information number 88, trip measuring system
phase L3
BOOLEAN
0
Information number 89, trip measuring system
neutral N
BOOLEAN
0
Information number 90, over current trip, stage low
BOOLEAN
0
Information number 91, over current trip, stage high
BOOLEAN
0
Information number 92, earth-fault trip, stage low
BOOLEAN
0
Information number 93, earth-fault trip, stage high
BOOLEAN
0
Autorecloser in progress (SMBRREC- INPROGR)
BOOLEAN
0
Faultlocator faultlocation valid (LMBRFLO-
CALCMADE)
Step
Default
1
128
Section 12
Monitoring
Description
Function type (1-255)
421