Table 316:
PULSETIMER Non group settings (basic)
Name
Values (Range)
t
13.7.6.4
Line distance protection REL650 2.2 IEC
Technical manual

Pulse timer function block PULSETIMER

The pulse (PULSETIMER) function can be used, for example, for pulse extensions
or limiting the operation time of outputs. The PULSETIMER has a settable length.
When the input is 1, the output will be 1 for the time set by the time delay
parameter t. Then it returns to 0.

Function block

PULSETIMER
INPUT
IEC04000407-3-en.vsd
IEC04000407 V3 EN-US
Figure 259:
PULSETIMER function block

Signals

Table 314:
PULSETIMER Input signals
Name
INPUT
Table 315:
PULSETIMER Output signals
Name
OUT

Settings

Unit
0.000 - 90000.000
s

Technical data

Table 317:
Number of PULSETIMER instances
Logic block
PULSETIMER
OUT
Type
Default
Description
BOOLEAN
0
Input to pulse timer
Type
Description
BOOLEAN
Output from pulse timer
Step
Default
0.001
0.010
Quantity with cycle time
Range or Value
3 ms
8 ms
100 ms
10
10
20
(0.000–90000.000) s
Section 13
PID-6985-INPUTSIGNALS v1
PID-6985-OUTPUTSIGNALS v1
Description
Time delay of function
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1
Accuracy
±0.5% ±10 ms
Logic
IP11016-1 v2
M11466-3 v3
M11465-3 v4
PID-6985-SETTINGS v1