58 Technical data
•
Number of PTC thermistors: 1, 3 or 6 in series (in both inputs)
•
Triggering threshold: 3.6 kohm ±10%
•
Recovery threshold: 1.6 kohm ±10%
•
PTC terminal voltage: < 5.0 V
•
PTC terminal current: < 1 mA
•
Short-circuit detection (start-up and in normal operation): 0 ... 50 ohm, min. 0 ...
10 ohm). For the effect of the cable length, see above.
STO output connection
■
•
Maximum wire size:
2
•
2.5 mm
(14 AWG) without FSO module
2
•
1.5 mm
(16 AWG) with FSO module
•
Maximum wire length: 30 m (98 ft) for the whole loop
•
Tightening torque: 0.5 N·m (4.4 lbf·in)
•
Contact rating: 24 V DC (17 ... 30 V), 1 A / channel
•
Maximum breaking capacity: 1000 VA
Ambient conditions
For the environmental limits for the safety functions and the drive, refer to the drive
hardware manual.
Safety data
The FPTC-02 module is a type A safety component as defined in IEC 61508-2. For the
types of the drive/inverter STO and the FSO module, see the applicable hardware
manual or FSO user's manual.
The table gives the safety data for the SMT function with different configurations.
The calculations are based on the worst case data of the drive Safe torque off (STO)
function. The PFH/PFD
of the FSO module. The FSE-31 module is included in the calculations for the FSO
module.
Note: The failure rate of the PTC sensor is not included in the calculations.
These are the configurations in the table:
1.
FPTC module + drive STO, two-channel configuration. See
1 (page
30).
2.
FPTC module + drive STO + FSO module with STO function request, two-channel
configuration. See
3.
FPTC module + drive STO + external safety relay, two-channel configuration. See
Wiring example 3 (page
4.
FPTC module + drive STO, one-channel configuration. See
4 (page
33).
5.
FPTC module + drive STO + FSO module with STO function request, one-channel
configuration. See
values can be different based on the internal configuration
avg
Wiring example 2 (page
32).
Wiring example 5 (page
Wiring example
31).
Wiring example
34).