Parameter Copying Procedure - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Preparing for Operation and Monitoring
H Sequence of Display
Note The following display is an example of the capacity displayed. The values in parentheses indicate
the capacities for European motors.
Voltage class
2: 3-phase 200 V
b: Single-phase 200 V
4: 3-phase 400 V

3-2-2 Parameter Copying Procedure

• To copy parameter values to another Inverter, take the following steps.
1. Set n001 for parameter write-prohibit selection/parameter initialization to 4.
2. Set n177 for parameter read-prohibit selection to 1 so that the parameters can be read.
3. Read the parameter set value with the EEPROM of the Digital Operator with the item rED selected.
4. Turn OFF the Inverter and remove the Digital Operator.
5. Mount the Digital Operator to the Inverter to which the parameters are to be copied. Then turn ON
the Inverter.
6. Copy the data in the EEPROM to the Inverter with the item CPy selected.
Reading
Writing
Verifying
Inverter
capacity
Software
version
Max. applicable motor capacity
0.1: 0.1kW (0.1 kW)
0.2: 0.25 kW/0.37 kW (0.2 kW)
0.4: 0.55 kW (0.4 kW)
0.7: 1.1 kW (0.75 kW)
1.5: 1.5 kW (1.5 kW)
2.2: 2.2 kW (2.2 kW)
3.7: 3.7 kW (3.7 kW)
5.5: 5.5 kW (5.5 kW)
5: 7.5 kW (7.5 kW)
Note The values in parentheses indicate Japanese
motor capacities.
Chapter 3
Completed
reading
or
Completed
writing
or
Completed
verifying
or
or
or
3-11