Selection Data; Specifications - Mitsubishi Heavy Industries SRK25GZ-L1 Handbook

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDKN-C

13.2 SELECTION DATA

13.2.1 Specifications

Model FDKNP208CEN-S
Item
Nominal cooling capacity
(1)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
(4)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Indicates the value at mild mode.
506
Model
W
kW
A
%
A
dB(A)
mm
kg
kW
Louver fins & inner grooved tubing
kg
r
W
CMM
Long life filter × 2 (washable)
Rubber sleeve (for fan motor)
W
Wireless remote control switch
Internal thermostat for fan motor.
mm
(in)
Item
Indoor air temperature
DB
27˚C
FDKNP208CEN-S
FDKN208C
4850
1 Phase, 220/240V, 50Hz
2.03/2.09
9.4/9.5
98/92
55
Hi:45 Lo:38
275 × 790 × 179
10
R407C
Holding charged
Tangential fan × 1
26 × 1
Line starting
Hi:16 Lo:10
Unavailable
Thermostat by electronics
Frost protection thermostat.
Liquid line: φ6.35 (1/4") Gas line: φ15.88 (5/8")
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Outdoor air temperature
WB
DB
19˚C
35˚C
FDCP208CEN3
52
690 × 880 × 290
49
RM5523HNE5 × 1
1.7
Line starting
Slitted fines & bare tubing
Capillary tube
0.87 [Pre-charged up to the piping length of 5m]
0.7 (MA32)
Propeller fan × 1
55 × 1
Line starting
55
Rubber mount (for compressor)
20 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Thermistor for discharge temperature.
High pressure switch for protection.
Standards
WB
24˚C
ISO-T1, JIS B8616

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents