(2) Outdoor unit
Models SCM802HENG-L, 1002HENG-L
Item
Cooling capacity
Heating capacity
Power source
Power consumption
Running current
(4)
Noise level
Exterior dimensions
Height × Width × Depth
Color
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Refrigerant control
Refrigerant
Refrigerant oil
Air handling equipment
Fan type & Q'ty
Motor
Air flow (at high)
Shock & vibration absorber
Safety equipment
Size × Core × Number
Refrigerant
Connecting method
piping
Attached length piping
Insulation
Power source supply
Size × Core number
Connection
wiring
Connecting method
Accessories (included)
Indoor units to be combined
Notes (1) The data are measured at the following conditions.
Operation DB
Cooling
Heating
(2) The values for capacity and power consumption shown in a range ( ) indicate the minimum and maximum of the range.
(3) If the piping length exceeds 50 mm, additional charging is required. (20g/m)
(4) Expressed in sound pressure level.
Models
W
W
Cooling
W
Heating
Cooling
A
Heating
Cooling
dB (A)
Heating
mm
kg
kW
kg
R
W
CMM
mm (in)
Item
Indoor air temperature
DB
27ºC
20ºC
SCM802HENG-L
8000 (1500 ~ 8400)
10500 (1500 ~ 11000)
1 Phase
2990 (610 ~ 3240)
3190 (620 ~ 3450)
16.1 (3.2 ~ 17.8)
17.2 (3.2 ~ 18.3)
46
47
1000 × 950 × 340
Stucco white
119
GT-A5527EA43
2.0
Direct start
Capillary tubes + Electric expansion valve
R22
(Pre-charged up to the piping length of 50m)
1.45 (BARREL FREEZE 32SAM)
Propeller fan × 2
24
53
Rubber (for compressor)
Compressor overheat protection, Overcurrent protection
Power transistor overheat protection
Liquid line: φ 6.35 (1/4") × 4
Gas line: φ 9.52 (3/8") × 2 + φ 12.7 (1/2") × 2
Flare connecting
Necessary (Both Liquid & Gas lines)
Terminal block (Screw fixing type)
× 4 cores (Including earth cable)
2
1.5 mm
Terminal block (Screw fixing type)
Union : (φ 9.52 / φ 12.7) × 2, (φ 12.7 / φ 9.52) × 2
Installation sheet, Manual instruction
SKM22, 25, 28, 32, 40, 50 type
SRRM40 type
Outdoor air temperature
WB
DB
19ºC
35ºC
7ºC
SCM-HG
(4 room)
SCM1002HENG-L
10000 (1500 ~ 10300)
12000 (1500 ~ 12200)
50Hz
4200 (610 ~ 4570)
3750 (620 ~ 3770)
22.5 (3.2 ~ 25.0)
20.5 (3.2 ~ 21.1)
Standards
WB
24ºC
JIS C9612, ISO-T1
6ºC
JIS C9612, ISO-T1
109