Selection Chart - Mitsubishi Heavy Industries SRK25GZ-L1 Handbook

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDU-C

16.2.6 Selection chart

Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following
way.
Net capacity = Capacity shown on specification × Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
(a) Only case of ISO-T1 models.
Cooling
Applicable range
ISO-T1 Standard condition
Indoor air W.B. temperature(˚CW.B.)
643