Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 751

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

(i)
Floor standing hidden type (FDFU)
Models FDFUJ28HKXE2, 45HKXE2, 56HKXE2, 71HKXE2
Item
1
Nominal cooling capacity*
2
Nominal heating capacity*
Power source
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Outdoor units to be combined
Notes
(1) The data are measured at the following conditions.
Item
Operation
1
Cooling*
2
Heating*
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
Model
(3)
FDFUJ28HKXE2
W
2800
W
3200
dB(A)
Hi: 41 Me:38 Lo: 36
mm
kg
W
30 1
CMM
Hi: 12 Me: 11 Lo: 10
Liquid line: 6.35(1/4"),
mm(in)
Gas line: 12.7(1/2")
FDCJ140HKXE2B, 224HKXE2B, 280HKXE2B, FDCP140HKXE2B, 224HKXE2B, 280HKXE2B
Indoor air temperature
DB
WB
27
19
20
(3)
FDFUJ45HKXE2
FDFUJ56HKXE2
4500
5000
1 Phase 220/240V 50Hz
Hi: 43 Me:41 Lo: 40
630
1077
225
25
Louver fins & inner grooved tubing
Electronic Expansion Valve + Capillary tube
Centrifugal fan 2
Line starting
Hi: 14 Me: 12 Lo: 10
Not possible
Polypropylene net
2(Washable)
Rubber sleeve(for fan motor)
Polyurethane foam
Remote control switch (Optional:RCD-HKXFL-E2)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Flare piping
Connectable with VP20
Necessary (both Liquid & Gas lines)
Mounting kit
_
Outdoor air temperature
DB
WB
35
24
7
6
FDC-HKX
(3)
FDFUJ71HKXE2
5600
7100
6300
8000
630
1362
225
32
40 1
Hi: 18 Me: 15 Lo: 12
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
Standards
ISO-T1,JIS B8616
749
(3)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents