(d) Location where strong wind blows against the unit
1)
Install the unit directing the
discharge air port to the wall.
(Only case of FDC(P)208~508 type)
(2) Carry-in and installation of unit
Pay sufficient attention to the carry-in and moving work of the unit, and always execute work by two persons or more.
(a)
Carry-in
1)
When carrying-in the unit, carry it in as packed condi-
tion to the installation site as near as possible.
2)
If you are compelled to carry-in the unit unpacked con-
dition, lift the unit by the rope using a nylon sling or
applying protection plates so that the unit is not marred.
¡ Rope the unit taking the discrepancy of center of gravity into consideration.
CAUTION
(b) Moving
1)
The unit is heavier on the right side looking from the front of unit
(discharge air port side). Therefore, sufficient caution is required for
the person who carries the right side of unit. The person who carries
the left side must hold the handle of front panle and the conner pillar
with both hands.
(c) Bolt securing position
Models FDC(P)208~508 type
Intake
Discharge
Anchor bolt position
(4 places)
1)
To install the unit, secure the legs of unit by below mentioned bolts without fail.
Models FDC(P)208~508 type
Make the found-
ation wider.
2)
Limit the protrusion height of front side anchor bolts to 15 mm at the maximum.
3)
Install the unit firmly so that it does not fall by earthquake and strong wind.
4)
Make the concrete foundation by referring the above illustration.
5)
Install the unit in level. (The height difference between right and left is within 30 mm.)
2)
Install the unit directing the
discharge air port at a right
angle to the wind direction.
Wind
direction
Item
Model
FDC(P)208
FDC(P)258, 308
FDC(P)408, 508
Secure with bolts.
(M10 to 12)
Bury the foundation deeper
into the ground.
3)
Where the foundation is not stable, secure the
unit with wire, etc.
Models FDC(P)208~508 type Models FDC808, 1008 type
Wind
direction
Secure with the anchor bolt.
Models FDC(P)208~508 type
Protection plate
Wood base
Unit : mm
Models FDC808, 1008 type
A
B
C
150
150
380
150
150
330
165
175
380
Anchor bolt
position
(4 locations)
Models FDC808, 1008 type
Make the width
wide.
FDT ( N ) -H
Fasten with anchor bolts
Models FDC808, 1008 type
Hanging hook
Heavier on
Conner
the right side
pillar
(Service panel side)
Fasten with a
bolt (M10).
Sink the
foundation
deeply.
Wire
339