Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 385

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

(3) Outdoor unit
Models FDC208CEN3, FDCP208CEN3
Opening for piping and
electric wiring
150
55
260
Required space for maintenance and air flow
L
2
Air
inlet
Maintenance
space
Notes
(1) Avoid the location where four sides are entirely surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict the protrusion length of anchor bolt to 15 mm and under.
(3) When strong wind blows against the unit, direct the discharge port at a right angle to the wind direction.
(4) Secure the space of 1 m and over at the top of unit.
(5) Make the height of obstruction wall in front of discharge port lower than the height of unit.
40
95
Terminal block
40
50
15
880
Holes for anchor bolt
(M10 × 4 pcs.)
580
150
50
15
335
Holes for drain
(M20 × 3 pcs.)
L
3
Air inlet
L
4
L
1
Air inlet
Liquid piping: φ6.35 (1/4˝)
(Flare connecting)
Gas piping: φ15.88 (3/8˝)
(Flare connecting)
Liquid piping: φ6.35 (1/4˝)
(Flare connecting)
Gas piping: φ15.88 (3/8˝)
(Flare connecting)
Opening for electric wiring
Electric wiring
Opening for
electric wiring
Opening for piping
and electric wiring
15
40
Minimum allowable space to the obstacles
Installation
type
Mark
L
1
L
2
L
3
L
4
FDT ( N ) -C
Unit: mm
Opening for piping and
electric wiring
50
27
50
50
Unit:mm
1
2
3
Open
Open
500
300
5
Open
100
150
100
5
5
5
383