Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 271

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

Model FDTN258HEN-S1
Item
Nominal cooling capacity
(1)
Nominal heating capacity
(1)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Heating input
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
(4)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Indicates the value at mild mode.
Model
FDTN258H
W
W
kW
A
%
kW
A
%
A
dB(A)
Hi: 39 Lo: 35
Unit 260 × 840 × 840
mm
Panel 30 × 950 × 950
kg
30 (Unit:24 Panel:6)
kW
Louver fins & inner grooved tubing
kg
Holding charged
r
Turbo fan × 1
25 × 1
W
Line starting
CMM
Hi:16 Lo:11
Available
Long life filter ×1(washable)
Rubber sleeve (for fan motor)
W
Wireless remote control switch
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
Liquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
(in)
(Connectable with VP25)
Mounting kit. Wireless remote controller. Drain hose
Indoor air temperature
DB
WB
27˚C
19˚C
20˚C
FDTN258HEN-S1
FDC258HEN3A
5700
6100
1 Phase, 220/240V, 50Hz
2.05/2.16
9.4/9.4
99/96
1.95/2.10
9.1/9.2
97/95
51
845 × 880 × 340
RM5526GNE4 × 1
Line starting
Slitted fins & bare tubing
Capillary tube
R22
1.1 [Pre-charged up to the piping length of 5m]
0.7 (BARREL FREEZE 32SAM)
MC controlled de-icer
High pressure switch
Propeller fan × 1
Line starting
Rubber mount (for compressor)
20 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Abnormal discharge temperature protection
Flare piping
Necessary (both Liquid & Gas lines)
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
7˚C
6˚C
FDT ( N ) -H
52
55
1.9
55 × 1
56
Standards
ISO-T1, JIS B8616
269

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents