20.2.2 Range of usage & limitations
Item
Indoor intake air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor units
Number of connected units
that can be
used in
Total capacity
combination
Single direction piping lenght
Piping length after first division
Difference in
When above outdoor unit
height between
indoor and outdoor
When below outdoor unit
units
Difference in height between indoor units
Indoor unit atmosphere (behind ceiling)
temperrature and humidity
Compressor
1 cycle time
stop/start
Stop time
frequency
Voltage fluctuation
Power source
Voltage drop during start
voltage
Interval unbalance
Allowable length of refrigerant piping, Height difference between indoor and outdoor unit
Individual flow divide controller
(Max 70m )
Outdoor unit
Between the outdoor unit and first branch (main piping): Max 70m (actual length)
Between the first branch and each indoor unit : Max 30m (each indoor unit) (actual length)
Note (1)
The indoor unit and individual flow divide controller positions should be within the range of the reach of the
connections of the wires that come with the individual flow divide contoroller
966
System
FDCP2001HKXRE2
11000 to 29200w
Indoor unit
Individual flow divaide
First branch
controller
Refer to the selection chart.
1 to 8 units
Indoor unit MAX 100m
MAX 30m
MAX 50m
MAX 10m
MAX 15m
Dew point temperature 28
or less, relative humidity 80% or less
6 min or more(from stop to stop or from start to start)
3 min or more
+ _
Within
10% of rated voltage
+ _
Within
15% of rated voltage
+ _
Within
3% of rated voltage
Max
30m
Max
30m
(Lowest indoor unit)
FDCP2501HKXRE2
13200 to 37100w
(Highest indoor unit)