3)
Mount the unit on the mounting brackets.
5)
Assemble the side panels.
(b) Wall mounted installation
1)
Fix the mounting brackets on a wall.
Fixing bolts
Double nuts
Note (1) Location of the mounting brackets fixing bolts
are the same as those for the floor standing in-
stallation except the location height.
3)
Assemble the side panels.
(3) Drain piping
The drain piping can be directed to the floor or rear sides as follows.
(a) Connect a drain piping to the drain outlet and fix it by
use of tightening band.
Hole for piping
Mounting brackets
Unit fixing bolts
Install the suspension brackets so that this
plane will be level or will have a gentle incline
toward the right. (left and right side height
difference should be from 0 to 0.1 in.)
Mounting
brackets
Flat washers
Front cover
Drain hose (accessory parts)
Drain piping (purchased in a field)
Base
4)
Fix the unit on the floor by using the fixing brackets.
Fixing bracket
Base
2)
Suspend the unit on the mounting brackets.
Remove the base when
it is not required.
Note (1) The figure on the left shows the wall mounted
installation when the base is removed.
(b)
Indoor side drain piping must be thermally insulated.
(c)
After finishing the drain piping check the drainage
by pouring some water in the drain pan.
Decline
FDFL-H
Fix the bracket on the Base
by use of attached screws.
[M8 × 8l]
After that fix it on the floor
by use of flat washers and
double nuts.
Fixing bolts
Mounting brackets
Unit fixing bolts
Up-and-down bend
Bad
Bad
Trap