All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. These instructions do
not cover all variations for every kind of installation circumstance. Should further information be desired or should particular
problems occur, the matter should be referred to Mitsubishi Heavy Industries, Ltd.
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO
FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION
AND/OR PROPERTY DAMAGE.
14.5.1 Installation of indoor unit
(1) Preparation of indoor unit
Before of during the installation of the unit, assemble necessary optional panel, etc. depending on the specific type.
(2) Select places for installation satisfying following conditions and, at the same time, obtain the consent on the
part of your client user.
(a) Places where chilled or heated air circulates freely.
When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases, suggest your client users to install
air circulators.
(b) Places where perfect drainage can be prepared and sufficient drainage.
(c) Places free from air disturbances to the suction port and blowout hole of the indoor unit, places where the fire alarm may not
malfunction or short-circuit.
(d) Places with the environmental dew-point temperature is lower than 28°C and the relative humidity is less than 80%.
When installing at a place under a high humidity environment, pay sufficient attention the prevention of dewing such as
thermal insnlation of the unit proper.
(e) Ceiling height shall have the following height.
Models
Panel
Combination with
silent panel
Combination with
canvas panel
(3) Avoid installation and use at those places listed below.
(a) Places exposed to oil splashes or steam (e.g. kitchens and machine plants.)
Installation and use at such places incur deteriorations in the performance or corrosion with the heat exchanger or damage in
molded synthetic resin parts.
(b) Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner, gasoline, etc) in generated or remains.
Installation and use at such places cause corrosion in the heat exchanger and damage in molded synthetic resin parts.
(c) Places adjacent to equipment generating electromagnetic waves or high-frequency waves such as in hospitals.
Generated noise may cause malfunctioning of the controller.
FDR208,258,308
FDR408,508
365mm
416mm
459mm
510mm
NOTICE
through your local distributor.
WARNING
¡ Installation space.
100or
100or
more
Obstacle
FDR-H
more
50 or more
Unit mm