Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 463

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

Table of bypass factor
Model
Item
Hi
Air flow
Lo
(2) Correction of cooling capacity in relation to flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
(3) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way equivalent piping length between the indoor and outdoor
units.
Equivalent length
m
(1)
FDEN208 type
FDEN258 type
FDEN308 type
FDEN408 type
FDEN508 type
Note (1) Equivalent piping length can be obtained by calculating as follows.
208, 258, 308 series [φ15.88(5/8")]: Equivalent piping length = Real piping length + (0.10 × Number or bends in piping)
408, 508, series [φ19.05(3/4")]: Equivalent piping length = Real piping length + (0.15 × Number of bends in piping)
[Equivalent piping length < Limitation length of piping + 5m]
(4) When the outdoor unit is located at a lower height than the indoor unit in cooling operation, the following values
should be subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
Piping length limitations
Model
Item
Max.one way piping length
Max.vertical height difference
Note (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
How to obtain the cooling capacity
Example : The net cooling capacity of the model FDENP308CEN-S with the air flow "High", the piping length of 15m, the outdoor
unit located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0 ˚C and outdoor dry-bulb temperature 35 ˚C
is
Net cooling capacity =
FDEN208C
FDEN258C
0.031
0.030
0.016
0.013
5
10
15
1.0
0.995
0.995
1.0
0.995
0.99
0.985
1.0
0.99
0.98
1.0
0.995
0.985
1.0
0.99
0.975
0.965
FDEN208, 258 type
30m
20m(Outdoor unit is higher)
15m(Outdoor unit is lower)
×
7100
1.00
FDENP308CEN-S Air flow
"High"
FDEN308C
0.036
0.018
20
25
30
35
0.99
0.985
0.985
0.98
0.98
0.975
0.97
0.97
0.96
0.95
0.94
0.98
0.97
0.965
0.955
0.95
0.94
0.925
5m
10m
15m
0.01
0.02
0.03
×
×
(0.98 - 0.01)
Length 15m.
Height difference 5 m
FDEN-C
FDEN408,508C
0.018
0.010
40
45
50
55
_
_
_
_
_
_
_
_
0.93
0.92
0.91
0.9
0.95
0.94
0.935
0.925
0.915
0.9
0.89
0.875
FDEN308, 408, 508 type
50m
30m(Outdoor unit is higher)
15m(Outdoor unit is lower)
1.0
=
6887 w
Factor by air
temperatures
461