Installation Of Outdoor Unit - Mitsubishi Heavy Industries SRK25GZ-L1 Handbook

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

SCM-C
[When the pipe is extended to left and taken out from the rear center]
(Drain pipe relocation procedure)
1. Remove the drain pipe.
¡ Loosen the spring clamp to
remove.
¡ When arranging the pipe through a hole opened at the
center, open the knockout hole using nippers, etc.
(4) Installation on indoor unit
(a) Install the indoor unit on the mounting plate.
Hook the upper part of the indoor unit on the stoppers disposed at the upper part of the mounting plate and lightly push the
lower part of the indoor unit so that the unit is fixed in position.
¡
When removing the indoor unit
1
Disconnect the lid at right and left.
2
Pull down the stoppers (right and left)
provided at the bottom of the indoor unit
base. (See the detail view shown at right.)
(The stoppers are separated from the
mounting plate.)
(b)
Be sure not to leave any trap on the drain pipe.
Declining slope

7.5.3 Installation of outdoor unit

(1) Make sure that the unit is stable in installation. Fix the unit to stable base.
(2) In wiring, make sure that the wire terminal numbers are match to the wire terminal numbers of indoor unit terminal block.
(3) Terminal symbol A of the outdoor unit is used for A indoor unit and B for B indoor unit.
Earth wiring
(yellow/green)
Interconnecting wiring
Wiring clamp
254
2. Remove the drain cap.
3. Insert the drain cap.
¡ Remove by hand or use
¡ Securely insert the drain
cutting pliers, etc.
Note: If it is inserted
Inverted slope
Trap
A unit
B unit
Indoor side
Outdoor side
Terminal block
Earth terminal
Interconnecting wire
4. Connect the drain pipe.
¡ Loosen the spring clamp
cap removed in the step 2.
and securely insert the
drain pipe.
insufficiently, water
Note: If it is inserted
leakage could result.
insufficiently, water
leakage could result.
Note (1) It is designed to collect moisture
accumulated on the rear face in the
drain pan. Be sure not to
accommodate the power cable, etc.
above the chute.
Light push
Indoor unit base bottom stopper
(2 places at right, left)
Power supply
220-240V~50Hz
Earth terminal
CENELEC code for cables required
field cables.
Power wiring
Chute
Wall
Pipe accommodation space
Mounting
plate
Wall
POWER SUPPLY CODE
H05RNR3G 3.5