Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 326

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDT ( N ) -H
17) Drain detection
(Only FDTN(P), FDT, FDR models)
a)
If there is detection of a drain abnormality during cooling operation, the drain pump goes ON for 5 minutes and the compres-
sor which had been running comes to a stop.
Overflow detection is carried out at all times with the float switch regardless of operational mode. If an overflow is generated
(or if the float switch is not yet connected or has been disconnected). there is emergency stop (while the Check lamp (yellow)
blinks 4 times) the drain motor operates until reset of the float switch.
b)
If a drain abnormality is detected during cooling operation, there is emergency stop (while the Check lamp (yellow) blinks 4
times) to stop the compressor, and the drain pump is operated with the drain motor until reset of the float switch.
c)
If a drain abnormality is detected during a stop state or fan operation, there is forced operation of the drain pump for 5
minutes. After 5 minutes have elapsed, the drain motor stops if the float switch is reset. Otherwise, there is emergency stop
(wile the Check lamp (yellow) blinks 4 times) and the drain motor operates until the float switch is reset.
d)
If the float switch is not connected or if there is a disconnection, there is emergency stop.
18) Low voltage guard control
If the power source voltage remains at a value of 80% of rating or less for 3 continuous minutes during operation of the compressor,
the compressor stops (52C OFF). Furthermore, if the power source voltage remains at a figure of 15% of rating or greater after 3
minutes have elapsed since stopping the compressor, there is restarting of the compressor (52C ON). Moreover, during stoppage of
the compressor, the Run lamp (green) blinks 2 times.
Note (1) When starting the compressor for the first time after turning the operational switch ON, there is starting regardless
of the power source voltage. Furthermore, if dip switch SW 3-2 on the internal substrate is OFF, this becomes
invalid. (Switch SW 3-2 is set to ON upon shipment from the factory).
19) Refrigerant shortage error
When 52C is ON when operating in cooling (including automatic cooling), if heat exchanger sensor temperature for the indoor
-R) does not drop to 25 °C or less for 40 minutes 5 minutes or more after the start of operation, an abnormal stop due to
unit (Th
I
insufficient refrigerant is performed.
20) External control (remote display)/control of input signal
¡ External control (remote display) output
Following output connectors (CNT) are provided on the control circuit board of indoor unit.
¡ Operation output: Power to engage DC 12V relay (provided by the customer) is outputted during operation.
¡ Heating output: Power to engage DC 12V relay (provided by the customer) is outputted during the heating operation.
¡ Compressor ON output: Power to engage DC 12V relay (provided by the customer) is outputted while the compressor is
operating.
¡ Error output: When any error occurs, the power to engage DC 12V relay (provided by the customer) is outputted.
¡ Control of input signal
(Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote
control unit.)
Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor
unit.
However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
324