Model FDENP308CES-S
Item
(1)
Nominal cooling capacity
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
(4)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 380/415V 50Hz.
(4) Indicates the value at mild mode.
Model
FDEN308C
W
kW
A
%
A
dB(A)
Hi:45 Lo:39
Unit 260 × 840 × 840
184 × 1260 × 650
mm
Panel 30 × 950 × 950
kg
27
kW
Louver fins & inner grooved tubing
kg
Holding charged
r
Multiblade centrifugal fan × 4
35 × 2
W
Line starting
CMM
Hi:16.5 Lo:11.5
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
W
Wireless remote control switch
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
Liquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
(in)
(Connectable with VP20)
Indoor air temperature
DB
WB
27˚C
19˚C
FDENP308CES-S
7100
3 Phase, 380/415V, 50Hz
3.14/3.29
5.5/5.8
87/79
45
GT-A5534HS41 × 1
Slitted fines & bare tubing
R407C
1.63 [Pre-charged up to the piping length of 5m]
Rubber mount (for compressor)
33 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Thermistor for discharge temperature.
High pressure switch for protection.
Flare piping
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
FDEN-C
FDCP308CES3
52
845 × 880 × 340
73
2.5
Line starting
Capillary tube
1.45 (MA32)
Propeller fan × 1
55 × 1
Line starting
58
Standards
ISO-T1, JIS B8616
447