Model FDU308CES-A
Item
(1)
Nominal cooling capacity
ISO-T1
ISO-T3
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Available static pressure
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Cooling
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 380V 50Hz/415V 50Hz/380V 60Hz.
Model
FDU308-A
W
kW
A
%
kW
A
%
A
dB(A)
41/43
360 × 820 × 830
mm
48
kg
kW
Louver fins & inner grooved tubing
kg
Holding charged
r
Multiblade centrifugal fan × 2
130 × 1
W
Line starting
CMM
20/24
Pa
Standard: 100 (10), Max 200 (20)
(mmAq)
Available
Field purchased
Rubber sleeve (for fan motor)
W
Remote control switch
(Optional: RCD-C-E)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
Liquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
(in)
(Connectable with VP25)
Indoor air temperature
DB
WB
27˚C
19˚C
29˚C
19˚C
FDU308CES-A
7100/7700
5700/6000
3 Phase, 380-415V 50Hz, 380V 60Hz
3.05/3.06/3.64
5.9/6.0/7.1
79/71/78
3.24/3.25/3.87
6.3/6.4/7.6
78/71/77
43
844 × 950 × 340
RC5538ESE1 × 1
Slitted fins & bare tubing
R22
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Propeller fan × 1
Rubber mount (for compressor)
– (Indoor unit side)
Internal protector for compressor.
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Flare piping
Necessary (both Liquid & Gas lines)
Mounting kit.
Outdoor air temperature
DB
WB
35˚C
24˚C
46˚C
24˚C
FDU-C
FDC306CES3
56
67
2.24
Line starting
Capillary tube
60 × 1
Line starting
54/56
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
631