FDC-HKX
(c) 1-way outlet ceiling recessed type (FDTS)
Models FDTSJ22HKXE2B, 28HKXE2B, 36HKXE2B
Item
1
Nominal cooling capacity*
2
Nominal heating capacity*
Power source
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Outdoor units to be combined
Notes
(1) The data are measured at the following conditions.
Item
Operation
1
Cooling*
2
Heating*
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Model
FDTSJ22,28,36 type
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for Europern nations which
require CE marking.
734
Model
FDTSJ22HKXE2B
W
2200
W
2500
dB(A)
Hi: 39 Lo: 38
mm
Kg
W
CMM
Hi: 11 Lo: 8
mm(in)
FDCJ140HKXE2B,224HKXE2B,280HKXE2B,FDCP140HKXE2B,224HKXE2B,280HKXE2B
Indoor air temperature
DB
WB
27
19
20
Item
Panel Part No.
With Auto Swing
TS-PSA-26W-E
(3)
(3)
FDTSJ28HKXE2B
2800
3200
1 Phase 220/240V 50Hz
Hi: 40 Me: 39 Lo: 38
Unit:194
1040
650
Panel:10
Unit:26 Panel:6
Louver fine & inner grooved tubing
Electronic Expansion Valve +Capillary tube
Centrifugal fan 2
35
1
Line starting
Hi: 12 Me: 11 Lo: 10
Possible
Long life filter
1(Washable)
Rubber sleeve(for fan motor)
Polyurethane foam
Remote control switch (Optional:RCD-HKX-S-E2)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Liquid line: 6.35(1/4"),Gas line: 12.7(1/2")
Flare piping
Connectable with VP25
Necessary (both Liquid & Gas lines)
Mounting kit
Decorative Panel
Outdoor air temperature
DB
WB
35
24
7
6
(3)
FDTSJ36HKXE2B
3600
4000
1290
770
Standards
ISO-T1,JIS B8616