Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 586

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDU-H
Model FDU408HES-SA
Item
(1)
Nominal cooling capacity
Nominal heating capacity
(1)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Heating input
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Available static pressure
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
nal thermostat for fan motor.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 380/415V 50Hz.
584
Model
W
W
kW
A
%
kW
A
%
A
dB(A)
mm
kg
kW
Louver fins & inner grooved tubing
kg
r
Multiblade centrifugal fan × 2
W
CMM
Pa
Standard: 100 (10), Max 200 (20)
(mmAq)
Rubber sleeve (for fan motor)
W
Internal thermostat for fan motor.
Frost protection thermostat.
mm
(in)
Item
Indoor air temperature
DB
27˚C
20˚C
FDU408HES-SA
FDU408-A
10000
11200
3 Phase, 380/415V 50Hz
4.68/4.78
8.1/8.4
87/79
4.06/4.10
7.4/7.8
83/73
53
44
360 × 820 × 830
49
Capillary tube
R22
Holding charged
MC controlled de-icer
High pressure switch
200 × 1
Line starting
27
Available
Field purchased
Wired remote control switch
(Optional: RCD-H-E)
Thermostat by electronics
Liquid line: φ9.52 (3/8") Gas line: φ19.05 (3/4")
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit.
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
FDC408HES3
54
1050 × 920 × 340
90
GU-A5550ES41 × 1
2.8
Line starting
Slitted fins & bare tubing
1.7 [Pre-charged up to the piping length of 5m]
1.6 (BARREL FREEZE 32SAM)
Propeller fan × 2
40 × 2
Line starting
70
Rubber mount (for compressor)
40 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Inter-
Abnormal discharge temperature protection.
Standards
WB
24˚C
ISO-T1, JIS B8616
6˚C

Hide quick links: