FDKN-H
(2) Alternative refrigerant R407C use models
Model FDKNP208HEN-S
Item
Nominal cooling capacity
(1)
Nominal heating capacity
(1)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Heating input
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
(4)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Indicates the value at mild mode.
474
Model
W
W
kW
A
%
kW
A
%
A
dB(A)
mm
kg
kW
Louver fins & inner grooved tubing
kg
r
W
CMM
W
Wireless remote control switch
Internal thermostat for fan motor.
mm
(in)
Item
Indoor air temperature
DB
27˚C
20˚C
FDKNP208HEN-S
FDKN208H
4850
5400
1 Phase, 220/240V, 50Hz
2.07/2.14
9.5/9.6
99/93
1.97/2.11
9.3/9.5
96/93
44
Hi: 45 Lo: 38
275 × 790 × 179
10
Capillary tube
R407C
Holding charged
IC controlled de-icer
High pressure switch
Tangential fan × 1
26 × 1
Line starting
Hi:16 Lo:10
Unavailable
Long life filter ×2(washable)
Rubber sleeve (for fan motor)
Thermostat by electronics
Frost protection thermostat.
Liquid line: φ6.35 (1/4") Gas line: φ15.88 (5/8")
Flare piping
(Connectable with VP16)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller. Drain hose
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
FDCP208HEN3A
52
690 × 880 × 290
49
RM5523HNE5 × 1
1.7
Line starting
Slitted fins & bare tubing
0.98 [Pre-charged up to the piping length of 5m]
0.7 (MA32)
Propeller fan × 1
55 × 1
Line starting
56
Rubber mount (for compressor)
20 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Thermostat for discharge temperature.
High pressure swich for protection
Standards
WB
24˚C
ISO-T1, JIS B8616
6˚C