(4) Indoor and outdoor signal wiring
(a) If only one Outdoor unit is used
Outdoor signal teminal block
Indoor signal terminal block
Notes (1) The indoor and outdoor signal wiring are without polarity
(2) For connection to the terminal block, use as M3.5 (5/32) round eye-let terminal is shown below.
(b) If plural outdoor units are used
1)
A maximum of 48 indoor units can be connected by using the crossover wiring method, with 2 wires for
each side of the outdoor and indoor units.
2)
Indoor/outdoor wiring method for multiple floors.
Outdoor
unit
3)
Loop wiring is prohibited
Outdoor
Outdoor
unit
unit
Indoor
unit
A
B
A
B
B
A
7 mm or less
Outdoor unit
Outdoor unit
A B
A B
A B
A B
Indoor unit
Indoor unit
Outdoor
Outdoor
unit
unit
Indoor
Indoor
unit
unit
Indoor
Indoor
unit
unit
Outdoor
Outdoor
unit
unit
(No)
Indoor
Indoor
Indoor
unit
unit
unit
2
Double cores 0.75 ~ 2 mm
Total length of signal wires: 1000 m or less
A
B
B
B
B
A
A
A
Outdoor unit
Outdoor unit
A B
A B
Double cores 0.75 ~ 2 mm
Total length of signal wires: 1000 m or less
A B
A B
Indoor unit
Indoor unit
Outdoor
unit
Double cores 0.75 ~ 2 mm
Total length of signal wires: 1000 m or less
Indoor
unit
Indoor
unit
Loop wiring of signal wires is prohibited
Wiring at the Portion indicated by a
dotted line is prohibited.
FDC-HKX
A
B
Either of the above wiring is correct.
2
2
897