4.2.1 Specifications

(1) Indoor unit
(a) Wall mounted type
Models SKM222HENG-L, 252HENG-L, 282HENG-L
Item
Cooling capacity
Heating capacity
(3)
Noise level
Exterior dimensions
Height × Width × Depth
Color
Net weight
Air handling equipment
Fan type & Q'ty
Motor
Air flow (at high)
Air filter, Q'ty
Operation switch
Room temperature control
Pilot lamp
Safety equipment
Liquid line
O.D
Gas line
Refrigerant
Connecting method
piping
Attached length of piping
Insulation
Drain hose
Accessories (including)
Optional parts
Outdoor units to be combined
Notes (1) The data are measured at the following conditions.
Operation DB
Cooling
Heating
(2) Capacity indicated is the rated capacity with one unit operating under JIS standards conditions.
(3) Expressed in sound pressure level.
106
Models
SKM222HENG-L
W
W
Cooling
dB (A)
Heating
mm
kg
W
Cooling
CMM
Heating
mm (in)
Item
Indoor air temperature
DB
27ºC
20ºC
SKM252HENG-L
2200
2500
3200
3400
38
39
250 × 750 × 178
Ivory white
7.5
Tangential fan × 1
17
7.0
7.5
Polypropylene net × 2 (Washable)
Wireless-Remote controller
M.C thermostat
RUN (Green), TIMER (Yellow)
Frost protection, Serial error protection
Fan moter error protection
φ 6.35 (1/4")
φ 9.52 (3/8")
Flare connecting
Liquid line : 0.4m Gas line : 0.35m
Necessary (Both Liquid & Gas lines)
Connectable
Mounting kit
SCM802HENG-L,1002HENG-L
Outdoor air temperature
WB
DB
19ºC
35ºC
7ºC
SKM282HENG-L
2800
4000
39
40
275 × 790 × 174
18
7.7
9.1
Standards
WB
24ºC
JIS C9612, ISO-T1
6ºC
JIS C9612, ISO-T1