8)
Places exposed to oil splashes or steam (e.g. kitchens and machine plants.)
Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or
damage in molded synthetic resin parts.
9)
Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner, gasoline, etc.) is generated or remains.
Installation and use at such places will cause corrosion in the heat exchanger and damage in molded synthetic resin parts.
10) Place adjacent to equipment generating electromagnetic waves or high-frquency waves such sa in hospitals. Generated
noise may cause malfunctioning of the controller.
(b) Preparations for installation
1)
Ceiling hole and suspension bolt positions
a) The pattern sheet shrinks or expands as humidity changes, so check the actual size before use.
b) The ceiling hole sizes and suspension bolt sizes are shown in the following figure.
Dimension table
Mark
1
Models
FDTW28, 45, 56
1015
type
FDTW71, 90 type
1260
FDTW112, 140
1730
type
(c) Installation
For the suspension bolt, use four M10 or W 3/8 bolts and secure so that each bolt can withstand a 50 kg/f pullout load.
Use a suspension bolt length that extends approximately 95 mm for the ceiling surface.
1 Ceiling hole size
2 Suspension bolt pitch
40
3
Center panel
Unit : mm
2
3
4
885
468
417
1130
590
540
1600
825
775
90
4
Control box
70
50
FDC-HKX
845