Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 167

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

(7) Drain up kit
(a) Part No. : RDU12E
(b) Accessories
No.
Name
1
Drain pump
2
Drain hose
3
Hose clamp
4
Tapping screw
(c) Installation of drain up kit
455
Indoor unit
Control
267
(d) Installation of drain up kit
1)
Fix the drain up kit on the right side of the
inside unit with tap screws.
2)
Insert the drain hose fully and securely to
the drain sockets of the inside unit and the
drain up kit.
3)
Connect the drain up kit's connectors for the
drain pump (red color 2P) and the float
switch (black 2P) to the connectors of the
control box. (The control box's connectors
for the drain pump and the float switch are
also red and blace respectively.) Note that
the control's connector for the float switch
is already connected to the inside unit's
connector for the float switch, so disconnect
them and connect it to the drain up kit's
connector for the float switch and fix it with the wire clamp.
Qty.
1
1
1
4
176
62
Fitting for drain hose
Vinyl chloride pipe VP-25
A
WH
BK
For indoor unit
WH
RD
RD
VIEW A
2 Drain hose
WH
For indoor unit
WH
BK
WH
For float switch
RD
For drain pump
RD
RD
SCM-HG
(4 room)
Unit: mm
4 Tapping screw
165

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents