Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 752

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDC-HKX
(2) Outdoor unit
(a) Alternative refrigerant R407C use models
Models FDCP140HKXE2B, 224HKXE2B, 280HKXE2B
Item
Power source
1
Nominal cooling capacity*
2
Nominal heating capacity*
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
compressor type & Q' ty
Motor
Starting method
Capacity control
Crankcase heater
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Shock & vibration absorber
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain
Insulation for piping
Accessories
Indoor units to be combined
Notes
(1) The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in JIS-B8616.
(2) The refrigerant quantity in the connecting pipe is not included Charge it additionally at the site.
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
Refrigerant distributor pipe set Number list (Optional)
Outdoor unit
FDCP140HKXE2B
FDCP224HKXE2B
FDCP280HKXE2B
Notes
(1) The flow divider pipe that should be used depends on the indoor unit total downstream capacity. (1 set is required for each flow division.)
(2) When there are 13 or more indoor units there are limits on the length of the piping after the flow division, so refer to the usage range.
750
Models
FDCP140HKXE2B
W
14000
W
16000
dB(A)
56
mm
1450
690
600
kg
150
GT-A5539HAS51
kW
3.5
%
100 ~ 25
W
33
kg
9
1.45 (MA32)
Centrifugal fan 1
W
100 1
CMM
90
Compressor overheat protection, overeurrent protection, power transformer overheating
Liquid line: 9.52(3/8")
mm(in)
Gas line: 19.05(3/4")
Hole for drain( 20
FDTJ28, 36, 45, 56, 71, 90, 112, 140type
FDTWJ28, 45, 56, 71, 90, 112, 140type
FDTSJ22, 28, 36, 45, 71type
FDRJ22, 28, 45, 56, 71, 90, 112, 140type
FDUMJ36, 45, 56, 71, 90, 112, 140type
FDEJ36, 45, 56, 71, 112, 140type
FDKJ22, 28, 36, 45, 56, 71type
FDFLJ28, 45, 71type
Number of combined indoor units
1~8
(2)
1~13
(2)
1~16
(3)
(3)
FDCP224HKXE2B
3 Phase 380/415V 50Hz
22400
25000
58
1450
250
GT-A5539HAS52
1
1
GT-A5539HS52
1
3.5
1, 2.2
1
Direct start
100 ~ 16
33
2
Louver fines & inner grooved tubing
Expansion Valve +Capillary tube
R407C
2.9 (MA32)
MC controlled De-Icer
Centrifugal fan 2
Direct start
Rubber mount (for compressor)
protection, abnormal high pressure protection
Liquid line: 12.7(1/2")
Gas line: 25.4(1")
Brazing
4pcs)
Hole for drain( 20
Necessary (both Liquid & Gas lines)
_
FDFUJ28, 45, 56, 71type
(1)
Flow divider pipe
(Total capacity after the flow division)
Downstream capacity 101 or less : DIS-2KX10-E
Downstream capacity 180 or less : DIS-2KX20-E
Downstream capacity 180 or more : DIS-2KX30-E
(3)
FDCP280HKXE2B
28000
31500
59
1350
600
275
GT-A5539HAS52
1
GU-A5570HS52
1
3.5
1, 3.75
1
100 ~ 12
33
1, 40
1
12
3.05 (MA32)
100 2
180
Liquid line: 12.7(1/2")
Gas line: 28.58(11/8")
8pcs, 50
1pcs)