(b) In the case that there is a wall above the unit
No. of units that can be installed are limited up to 3 units.
(Example : 5HP × 3 units, 10HP × 1 units + 5HP × 1 unit)
150 and over
(side blow)
200 and under
(side blow)
(c) Plural units installation (Single crosswise row installtion : No limitation in No. of units)
L2
Note (1) When the wall heights H1 and H3 exceed the limited value, keep dimensions for L1 and L3 as shown below.
L1 = H1 – 500(In the case of side blow, H1 1,000 irrespective of L1 dimension)
L3 = 300 + (H3–700) / 2
However, there is no limitation in wall height H3 if L3 exceeds 600.
(d) Plural units installation (Plural installation in lengthwise and crosswise rows)
Notes (1) Side blow is not allowed.
(2) Secure dimensions L1 and H1 at the service space side. Secure dimensions L3 and H3 at the suction side.
L2
500 and over
(oblique blow)
600 and over
L1
Wall height H3
Air inlet
L3
(Service space)
L1
Wall height H1
Wall height H3
L3
L4
W1
W2
W3
L1
Wall height H1
5 HP
(One-blower unit)
8 or 10HP
(Two-blower unit)
L2
L1 500
H1 1,000
L3
L2 0
H2 No limitation
L3 300
H3 700
L4 0
H4 No limitation
L4
FDC-HKX
L1 or L2 0
L1 + L2
500
L1 or L2 350
L1 + L2
750
L1 500
L2 1,000
L3 300
L4 1,000
H1 1,000
H2 No limitation
H3 700
H4 No limitation
885