V MULTI
Operation characteristics of each unit
Model
Item
Power input (kW)
Running current (A)
1 Total power input (kW)
(Cooling) 8.44 + 0.11+ 0.27 = 8.82 (kW)
(Heating) 6.44 + 0.11+ 0.27 = 6.82 (kW)
2 Total running current (A)
(Cooling) 14.2 + (0.6+1.4 × 2 ) 15.5 (A)
(Heating) 11.6 + (0.6 + 1.4 × 2 ) 12.9 (A)
3 Total power factor (%)
8.82 × 1000
(Cooling)
—
√
3 × 15.5 × 380
6.82 × 1000
(Heating)
—
√
3 × 12.9 × 380
18.2.2 Range of usage & limitations
Models All models
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
688
FDC808HES3
8.44/6.44
14.2/11.6
.
= .
3
.
= .
3
× 100 86 %
.
= .
× 100 80 %
.
= .
Model
Dew point temperature: 28˚C or less, relative humidity: 80% or less
FDT308-A
0.11/0.11
0.6/0.6
All models
Refer to the selection chart
Refer to the following
Rating ± 10%
Min. 85% of rating
Max. 10 times/h
Max. 3 minutes
(Cooling/Heating)
FDT508-A
0.27/0.27
1.4/1.4