Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 196

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

SCM-HG
(2 room)
(5) Comfort timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode
operation is selected, the comfort timer starts and determines the starting time of next operation based on the initial value of 15
minutes and the relationship between the room temperature at the setting time (temperature of room temperature thermistor) and
the setting temperature. (Max. 60 minutes)
Operation mode
3 < Room temp. – Setting temp.
At cooling
3 < Setting temp. – Room temp.
At heating
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature thermistor (Th
(2) This function does not actuate when the operation select switch is set at the dehumidifying as well as the dehumidifying in the auto mode.
However, the operation of item (1) above is performed during the dehumidifying in the auto mode.
(3) During the pleasant reservation operation, both the operation lamp and timer lamp illuminate and the timer lamp goes off after expiration of the timer, ON setting
time.
(Example) Heating
Setting temperature
Room temperature
(6) Cooling operation
(a) Summary
1)
Capacity control
Model
Capacity
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum
capacity of the outdoor unit, the demand capacity will be proportionally distributed.
2)
Outdoor unit speed control (28 ~ 120 rps)
Indoor unit instruction total speed value
28 rps or less
More than 28 rps, but 120 rps or less
More than 120 rps
Note (1) The indoor unit instruction total speed value is the total of the values from each unit in item (b).
(b) Mode switching
Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion
coefficient to the indoor unit instruction speed.
Model (Indoor)
Operation Mode
Automatic
High
Medium
Low
Hi power
Econo
194
Operation start time correction value (Min.)
1 < Room temp. – Setting temp. 3
+5
2 < Setting temp. – Room temp. 3
+5
Operation starting time
Time
15 min.
10 min.
5 min.
earlier
earlier
earlier
SCM452HENG-L
2.0 ~ 5.1 kW
22
25
28 ~ 58
28 ~ 68
28 ~ 58
28 ~ 68
28 ~ 44
28 ~ 50
28 ~ 30
28 ~ 32
58
68
28 ~ 34
28 ~ 36
No change
No change
Corrects the starting time of next operation by
calculating the temperature difference.
¡ If the difference (= Setting temperature – Room
temperature) is 4ºC, the correction value is found to be
+5 minutes from the table shown above so that the
starting time of next operation is determined as
follows:
15 min. earlier + 5 min. = 20 min. earlier
Current operation
start time
Setting time
SCM452CENG-L
2.0 ~ 5.1 kW
Decision speed
28 rps
28 to 120 rps
120 rps
28
28 ~ 88
28 ~ 88
28 ~ 60
28 ~ 30
86
28 ~ 50
Room temp. – Setting temp. 1
–5
Setting temp. – Room temp. 2
–5
-A).
I
Correction value
(rps)
32
40
28 ~ 96
28 ~ 110
28 ~ 96
28 ~ 118
28 ~ 70
28 ~ 100
28 ~ 34
28 ~ 40
96
108
28 ~ 40
28 ~ 50

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents