Selection Data; Specifications - Mitsubishi Heavy Industries SRK25GZ-L1 Handbook

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDC-HKXR

20.2 SELECTION DATA

20.2.1 Specifications

(1) Indoor unit
(a) Ceiling recessed type (FDT)
Models FDTJ28HKXE2, 36HKXE2
Item
1
Nominal cooling capacity*
2
Nominal heating capacity*
Power source
Noise level
Exterior dimensions
Height
Width
Depth
Net weight
Refrigerant equipment
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow(Standard)
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Outdoor units to be combined
Notes
(1) The data are measured at the following conditions.
Item
Operation
1
Cooling*
2
Heating*
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
Decorative Panel model (Optional)
Model
FDTJ28,36 type
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
940
Models
FDTJ28HKXE2
W
2800
W
3200
dB(A)
mm
kg
W
CMM
mm(in)
Indoor air temperature
DB
WB
27
19
20
Item
Panel Part No.
T-PSA-32W-E
(3)
1 Phase 220/240V 50Hz
Hi: 37 Me: 34 Lo: 33
Unit:260
840
840
Panel:30
Unit:24 Panel:7
Louver fine & inner grooved tubing
Electronic Expansion Valve +Capillary tube
Turbo fan 1
17 1
Line starting
Hi: 12 Me: 10 Lo: 9
Possible
Long life filter
1(Washable)
Rubber sleeve(for fan motor)
Polyurethane foam
Remote control switch (Optional:RCD-HKX-S-E2)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat
Liquid line: 6.35(1/4"), Gas line: 12.7(1/2")
Flare piping
Connectable with VP25
Necessary (both Liquid & Gas line)
Mounting kit
Decorative Panel
FDCP2001HKXRE2, 2501HKXRE2
Outdoor air temperature
DB
WB
35
24
7
6
(3)
FDTJ36HKXE2
3600
4000
950
950
Standards
ISO-T1,JIS B8616

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents