Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 632

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDU-C
16.2 SELECTION DATA
16.2.1 Specifications
Model FDU308CEN-A
Item
Nominal cooling capacity
(1)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Available static pressure
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Cooling
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 220 / 240V 50Hz.
630
Model
ISO-T1
W
ISO-T3
kW
A
%
kW
A
%
A
dB(A)
mm
kg
kW
Louver fins & inner grooved tubing
kg
r
Multiblade centrifugal fan × 2
W
CMM
Pa
Standard: 100 (10), Max 200 (20)
(mmAq)
Rubber sleeve (for fan motor)
W
Internal thermostat for fan motor.
Frost protection thermostat.
mm
(in)
Item
Indoor air temperature
DB
27˚C
29˚C
FDU308CEN-A
FDU308-A
7100
5700
1 Phase, 220/240V 50Hz
3.29/3.33
16.5/17.3
91/80
3.48/3.52
17.5/18.3
90/80
89
41
360 × 820 × 830
48
R22
Holding charged
High pressure regulator valve
130 × 1
Line starting
20
Available
Field purchased
Remote control switch
(Optional: RCD-C-E)
Thermostat by electronics
Liquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit.
Outdoor air temperature
WB
DB
19˚C
35˚C
19˚C
46˚C
FDC306CEN3
56
844 × 950 × 340
67
RC5532ENE1 × 1
2.24
Line starting
Slitted fins & bare tubing
Capillary tube
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
Propeller fan × 1
60 × 1
Line starting
54
Rubber mount (for compressor)
– (Indoor unit side)
Internal protector for compressor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Standards
WB
24˚C
ISO-T1, JIS B8616
24˚C
ISO-T3, SASO

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents