2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

2)
Louver motor does not operate
Inspect at the indoor unit side.
louver operate at
power on?
Operate more than
1 min. later
Is the louver
operated with the remote
It is normal
Turn off and back on again
if it stops with
the power and check the
2 pushes on LS
motion of LS
Does the louver
link push the LS till
a click sound is
Defective LS
Replacement
Defective indoor unit PCB
Replacement
3)
When the indoor unit blower does not operate
Inspect at the indoor unit side.
All of cooling,
blower heating, thermaldry
do not operate
Check FM
Is Voltage detected
between CNF
terminals?
Defective FM
1
(CF
)
Replacement
1
Does the
NO
YES
Repair the wire
YES
Normal
controller
NO
NO
Ajust LS lever and
check again
heard?
YES
NO
YES
1
(1)
NO
YES
, capacitor
NO
Is LM wire
broken?
YES
Replace LM
Note(1) LM: Louver motor
LS: Limit swich
When some modes only operate.
Defective indoor unit PCB
Replacement
Check with the Hi, Me, Lo of blower
mode.
Defective indoor unit PCB
Replacement
FDC-HKX
NO
Is LM
Defective indoor
locked?
unit PCB
YES
929