Range Of Usage & Limitations - Mitsubishi Heavy Industries SRK25GZ-L1 Handbook

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

FDT ( N ) -H
8.2.2 Range of usage & limitations
Models FDTN208, 258 (FDC208, 258 type), FDTNP208~508 (FDCP208~508 type)
FDT208~508 (FDC208~508 type)
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
Models FDT308~508 (FDC306~506 type)
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
286
Models
FDTN208, 258 (FDC208, 258 type)
FDT208, 258 (FDC208, 258 type)
FDTNP208, 258 (FDCP208, 258 type)
Dew point temperature: 28˚C or less, relative humidity: 80% or less
Max. 30m
Max. 20m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Models
Dew point temperature: 28˚C or less, relative humidity: 80% or less
FDT308~508 (FDC308~508 type)
FDTNP308~508 (FDCP308~508 type)
Refer to the selection chart
Max. 30m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Rating ± 10%
Min. 85% of rating
Max. 10 times/h
Max. 3 minutes
FDT308~508 (FDC306~506 type)
Refer to the selection chart
Max. 30m
Max. 15m
Rating ± 10%
Min. 85% of rating
Max. 10 times/h
Max. 3 minutes
Max. 50m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents