Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 589

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

Model FDU1008HES-SA
Item
Nominal cooling capacity
(1)
(1)
Nominal heating capacity
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Heating input
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
High pressure control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Available static pressure
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 380/415V 50Hz.
Model
FDU1008-A
W
W
kW
A
%
kW
A
%
A
dB(A)
49
360 × 1570 × 830
mm
kg
92
kW
Louver fines & inner grooved tubing
kg
Holding charged
r
Multiblade centrifugal fan × 4
230 × 1, 270 × 1
W
Line starting
CMM
68
Pa
Standard: 100 (10), Max: 200 (20)
(mmAq)
Available
Field purchased
Rubber sleeve (for fan motor)
W
Wired remote control switch
(Optional: RCD-H-E)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
Liquid line: φ15.88 (5/8") Gas line: φ28.58 (1 1/8")
(in)
Brazing
(Connectable with VP25)
Indoor air temperature
DB
WB
27˚C
19˚C
20˚C
FDU1008HES-SA
FDC1008HES3
25000
28000
3 Phase, 380/415V 50Hz
12.8/12.9
22.7/21.7
86/83
10.6/10.8
19.2/18.7
84/80
154
1450 × 1350 × 600
CB125 × 1
Line starting
Slitted fines & bare tubing
Capillary tube
R22
7.6 [Pre-charged up to the piping length of 5m]
4.4 (BARREL FREEZE 32SAM)
MC controlled de-icer
High pressure switch
Propeller fan × 2
Line starting
Rubber mount (for compressor)
70 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor
High pressure protection switch
Liquid line: Flare Gas line: Brazing
Necessary (both Liquid & Gas lines)
Mounting kit.
Outdoor air temperature
DB
WB
35˚C
24˚C
7˚C
6˚C
FDU-H
58
195
9.0
100 × 2
180
Standards
ISO-T1, JIS B8616
587

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk35gz-l1Srk502z-l1Srk502z-lSrk328henf-l2Srk408henf-l2Srk501henf-l ... Show all

Table of Contents