FDR-H
14.2.2 Range of usage & limitations
Models FDR208~508 (FDC208~508 type)
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
Models FDR308~508 (FDC306~506 type)
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
540
Models
FDR208, 258 (FDC208, 258 type)
Dew point temperature: 28˚C or less, relative humidity: 80% or less
Max. 30m
Max. 20m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Models
Dew point temperature: 28˚C or less, relative humidity: 80% or less
FDR308~508 (FDC308~508 type)
Refer to the selection chart
Max. 50m
Max. 30m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Rating ± 10%
Min. 85% of rating
Max. 10 times/h
Max. 3 minutes
FDR308~508 (FDC306~506 type)
Refer to the selection chart
Max. 30m
Max. 15m
Rating ± 10%
Min. 85% of rating
Max. 10 times/h
Max. 3 minutes