Mitsubishi Heavy Industries SRK25GZ-L1 Handbook page 215

2000 air conditioning & heat pump machinery handbook
Table of Contents

Advertisement

(3) Inspection procedures corresponding to detail of trouble
Thermistor error
Is connector connection good?
YES
Is sensor resistance value good?
YES
Replace PCB.
Comp. dome thermistor temperature characteristics
Temperature (˚C)
Resistance (kΩ)
0
164
5
127
10
99
15
78
20
62
25
50
30
40
35
32
40
26
45
21
50
17
55
14
60
12
65
10
Current cut
Does current cut operate when
operating inverter with compressor
wire disconnected?
YES
Is output voltage applied to all 3
phases of power transistor?
YES
Is there any shortcircuit?
YES
Inspect compressor.
NO
Correct connection.
NO
Replace thermistor.
Temperature (˚C)
Resistance (kΩ)
70
8.7
75
7.3
80
6.2
85
5.3
90
4.5
95
3.9
100
3.3
105
2.9
110
2.5
115
2.2
120
1.9
125
1.6
130
1.4
135
1.3
NO
Defective inverter
NO
Defective inverter
NO
Secure space for inlet
and outlet.
¡ Check compressor wiring visually.
¡ Check insulation resistance. (1 MΩ or over)
¡ Check coil wire resistance. (Few Ω)
[Broken thermistor wire,
connector poor connection]
Thermistor temperature characteristics
(Room temperature, indoor unit heat ex-
changer temperature, outdoor unit heat
exchanger temperature, outdoor tempera-
ture)
30
25
(Broken wire)
20
15
Resistance (kΩ)
10
5
–10
0
10
(Shortcircuit)
Temperature (˚C)
[Open phase on compressor output
terminal, compressor lock]
If check results are normal,
compressor is locked.
SCM-HG
(2 room)
20
30
40
50
60
70
213